What you need to pay attention to for the installation of Ruipute plate heat exchanger

2020-06-08 06:54:00 

Ruiputeplate heat exchanger has the advantages of high energy efficiency, easy cleaning, long service life and long adaptability, so now more and more people use plate heat exchanger, in order to make it more convenient for you to install plate heat exchanger, the following author to introduce the installation of plate heat exchanger need to pay attention to some places.

Ruiputeplate heat exchanger should be installed on a hard concrete foundation floor, which should have a floor drain. There should be sufficient space around the heat exchanger for observation and access. Connecting pipelines should be firmly supported, and long pipelines should have a gap at the bend to facilitate expansion and contraction. Check if the clamping nuts of the heat exchanger are loose before use and tighten them if necessary.

Alfa Laval plate heat exchanger

In the installation of the highest point of the pipeline should be equipped with an exhaust valve, filled with water will be discharged when the air in the pipeline. At the lowest point of the pipeline should be equipped with a discharge valve, which can be used to discharge stagnant water. A thermometer and a pressure gauge should be installed in the inlet and outlet pipelines of the heat exchanger to observe its condition during operation.

When the medium is water-water heat exchange, on the hot water side, hot water enters through the interface of the heat exchanger and is discharged through the lower port; on the cold water side, cold water The main entry is from the lower port of the Ruiputeplate heat exchanger and the exit from the upper port. This is done in order to heat the heat exchanger internal hot and cold adjacent to the hot runner media flow in the opposite direction, i.e., "counter-current" heat transfer, so that the heat exchanger's The cold heat exchanger always maintains a more balanced temperature difference in the heat transfer process to facilitate heat transfer.

When the medium is steam-water heat transfer, steam enters through the upper interface of the heat exchanger, the lower interface discharges condensate, and the hot side of the heat exchanger is discharged. For single-stream assembly, do not install a trap at the condensate outlet to allow condensate to drain freely. (Many users install a trap at the condensate outlet to allow condensate to be discharged freely, resulting in low temperature of the water being heated). When there is a lot of steam in the discharged condensate, adjust the steam inlet valve of the heat exchanger to reduce the amount of steam supply. The discharged condensate is clean water and should be returned to the boiler for use. The cold water side should be entered from the lower end and discharged from the upper end.

The above is the author for you to introduce the installation of plate heat exchanger need to pay attention to some places, I hope it can help you, if you still want to know, you can come to consult us.